Programmable Logic Controller

KV-8000 series

Catalogs View Catalog

64-point Connector, with All Terminals Supporting 2-wire Sensors KV-C64XC

KV-C64XC - 64-point Connector, with All Terminals Supporting 2-wire Sensors

  • CE Marking
  • UL Listing(c/us)

Specifications

Model

KV-C64XC

Type

Input Unit

External connection method

Connector (MIL standard)*1

Input

Number of inputs

64 points

Input mode

24 VDC mode*2

Maximum input voltage

26.4 VDC

Rated input voltage

24 VDC, 4.1 mA

Minimum ON voltage

19 V

Maximum OFF current

1.5 mA

Maximum OFF voltage

-

Common method

32 points/1 common (2 terminals) × 2*3

Input time constant

[Input time constant setting 25 µs] OFF to ON: Typ. 25 µs/Max. 65 µs, ON to OFF: Typ. 75 µs/Max. 120 µs
[Input time constant setting 300 µs*4] OFF to ON: Typ. 275 µs/Max. 365 µs, ON to OFF: Typ. 275 µs/Max. 420 µs
[Input time constant setting 1 ms] OFF to ON: Typ. 1 ms/Max. 1.2 ms, ON to OFF: Typ. 1 ms/Max. 1.2 ms
[Input time constant setting 10 ms] OFF to ON: Typ. 10 ms/Max. 12 ms, ON to OFF: Typ. 10 ms/Max. 12 ms
(four-level switching)

Input impedance

5.6 kΩ

Internal current consumption

25 mA or less

Weight

Approx. 140 g

*1 Connectors for connector-type I/O units are not included XC Series Terminal Block Conversion Unit is available.
*2 All terminals are compatible with the 2-wire system (However, EV Series 2-wire system proximity sensors are not supported).
*3 Although KV-C64XC has four common points, the H side (2 points) are the same, and the L side (2 points) are the same as internal points.
*4 Configurable only when KV-8000A/7500/7300/5500/5000/3000 is connected. Cannot be selected when connected to KV-1000/700.