Safety input / output unit GC-S84

GC-S84 - Safety input / output unit

  • CE Marking
  • UL Listing(c/us)
  • CSA

Specifications

Model

GC-S84

Input/output points

Safety inputs

8

Safety outputs

4 (PNP)

Safety relay output

-

AUX outputs

Test outputs

2

Safety input specifications

Input device

Contact output device or PNP output device

Input type

Type3

ON level (voltage/current)

Min. 11 V/2 mA

OFF level (voltage/current)

Max. 5 V/1.5 mA

Short-circuit current

Approx. 3 mA

Protection circuit

Surge protection circuit, wrong wiring protection circuit

Maximum cable length

Max. 100 m 328.1'

Safety output specifications

Output type

PNP transistor output (DC-13, Type 0.5, Protected outputs)*1

Maximum load current

500 mA

Residual voltage (during ON)

Max. 2.0 V

Leakage current (during OFF)

Max. 0.5 mA

Maximum capacitive load

0.5 µF

Load wiring resistance

Max. 2.5 Ω

Protection circuit

Overcurrent protection circuit, reverse connection protection circuit

Maximum cable length

Max. 30 m 98.4'

Safety relay output specifications

Output type

-

Rated load (resistance load)

Rated load (inductive load)

Relay output mechanical life

Maximum cable length

B10d

Test output specifications

Output type

PNP transistor output*2

Maximum load current

100 mA*2

Protection circuit

Overcurrent protection circuit, reverse connection protection circuit*2

Maximum cable length

Max. 100 m 328.1'*3*2

AUX output specifications

Output type

-

Maximum load current

Residual voltage (during ON)

Leakage current (during OFF)

Protection circuit

Maximum cable length

Applicable standards

EMC

EMS: IEC 61131-2/-6, EN61131-2/-6,EMI: IEC 61131-2, FCC Part15B Class A, ICES-003, Class A

Safety

IEC 61508, EN 61508 SIL3, IEC 62061, EN 62061 SIL CL3, ISO/EN 13849-1:2015 Cat. 4, PL e

Dimensions

22.2×95×90 mm 0.87"×3.74"×3.54" (W×D×H)

Power supply

Power voltage

24 VDC (-20 to +20%) Class 2

Power consumption

Max. 60 mA

Environmental resistance

Ambient temperature

−10 to +55 °C 14 to 131 °F (No freezing)

Storage temperature

-25 to +70 °C -13 to 158 °F (No freezing)

Relative humidity

5 to 85% (No condensation)

Operating altitude

Max. 2000 m 6561.7'

Overvoltage category

II

Pollution degree

2

Vibration resistance

Frequency: 5 to 9 Hz, Half amplitude: 3.5 mm 0.14"
Frequency: 9 to 150 Hz, Acceleration: 10 m/s2
10 times each in X, Y, Z directions

Shock resistance

Acceleration: 150 m/s2, Operating time: 11 ms, 3 times each in X, Y, Z directions

Material

Polycarbonate

Weight

Approx. 130 g

*1 Paragraph 6.4.6 Temporary overload of IEC 61131-2 supports up to 1.2 times the maximum load current.
*2 Test outputs do not comply with paragraph 6.4 of IEC 61131-2.
*3 When the test output is branched and connected to multiple safety input devices, the total branched cable length must not exceed 400 m 1312.3'.

Other Models