Safety relay output unit GC-S1R

GC-S1R - Safety relay output unit

  • CE Marking
  • UL Listing(c/us)
  • CSA

Specifications

Model

GC-S1R

Input/output points

Safety inputs

-

Safety outputs

Safety relay output

1 (3a)

AUX outputs

-

Test outputs

Safety input specifications

Input device

Input type

ON level (voltage/current)

OFF level (voltage/current)

Short-circuit current

Protection circuit

Maximum cable length

Safety output specifications

Output type

Maximum load current

Residual voltage (during ON)

Leakage current (during OFF)

Maximum capacitive load

Load wiring resistance

Protection circuit

Maximum cable length

Safety relay output specifications

Output type

Relay (3a) (Externally-protected outputs)*1

Rated load (resistance load)

250 VAC 6A / 30 VDC 6A*2

Rated load (inductive load)

240 VAC 2A (AC-15) / 24 VDC 1A (DC-13)

Relay output mechanical life

Resistance load (250 VAC 6A/30 VDC 6A): Min. 100,000 times
Resistance load (250 VAC 1A/30 VDC 1 A): Min. 500,000 times
Inductive load (AC-15: 240 VAC 2 A): Min. 100,000 times (cosø = 0.3)
Inductive load (DC-13: 24 VDC 1 A): Min. 100,000 times (L/R = 48 ms)

Maximum cable length

Max. 100 m 328.1'

B10d

With rated load: 400,000
With low load: 2,000,000

Test output specifications

Output type

-

Maximum load current

Protection circuit

Maximum cable length

AUX output specifications

Output type

Maximum load current

Residual voltage (during ON)

Leakage current (during OFF)

Protection circuit

Maximum cable length

Applicable standards

EMC

EMS: IEC 61131-2/-6, EN61131-2/-6,EMI: IEC 61131-2, FCC Part15B Class A, ICES-003, Class A

Safety

IEC 61508, EN 61508 SIL3, IEC 62061, EN 62061 SIL CL3, ISO/EN 13849-1:2015 Cat. 4, PL e

Dimensions

39.6×95×90 mm 1.56"×3.74"×3.54" (W×D×H)

Power supply

Power voltage

-

Power consumption

Max. 80 mA

Environmental resistance

Ambient temperature

−10 to +55 °C 14 to 131 °F (No freezing)

Storage temperature

-25 to +70 °C -13 to 158 °F (No freezing)

Relative humidity

5 to 85% (No condensation)

Operating altitude

Max. 2000 m 6561.7'

Overvoltage category

II (III for relay output part)

Pollution degree

2

Vibration resistance

Frequency: 5 to 9 Hz, Half amplitude: 3.5 mm 0.14"
Frequency: 9 to 150 Hz, Acceleration: 10 m/s2
10 times each in X, Y, Z directions

Shock resistance

Acceleration: 150 m/s2, Operating time: 11 ms, 3 times each in X, Y, Z directions

Material

Polycarbonate

Weight

Approx. 180 g

*1 To comply with the requirements of IEC61131-2, connect 10 A fast blow fuse (IEC 60217) in series to each contact.
*2 Check the derating characteristics described later.