Safety input unit GC-S16

GC-S16 - Safety input unit

  • CE Marking
  • UL Listing(c/us)
  • CSA

Specifications

Model

GC-S16

Input/output points

Safety inputs

16

Safety outputs

-

Safety relay output

AUX outputs

Test outputs

4

Safety input specifications

Input device

Contact output device or PNP output device

Input type

Type3

ON level (voltage/current)

Min. 11 V/2 mA

OFF level (voltage/current)

Max. 5 V/1.5 mA

Short-circuit current

Approx. 5 mA

Protection circuit

Surge protection circuit, wrong wiring protection circuit

Maximum cable length

Max. 100 m 328.1'

Safety output specifications

Output type

-

Maximum load current

Residual voltage (during ON)

Leakage current (during OFF)

Maximum capacitive load

Load wiring resistance

Protection circuit

Maximum cable length

Safety relay output specifications

Output type

Rated load (resistance load)

Rated load (inductive load)

Relay output mechanical life

Maximum cable length

B10d

Test output specifications

Output type

PNP transistor output*1

Maximum load current

100 mA*1

Protection circuit

Overcurrent protection circuit, reverse connection protection circuit*1

Maximum cable length

Max. 100 m 328.1'*2*1

AUX output specifications

Output type

-

Maximum load current

Residual voltage (during ON)

Leakage current (during OFF)

Protection circuit

Maximum cable length

Applicable standards

EMC

EMS: IEC 61131-2/-6, EN61131-2/-6,EMI: IEC 61131-2, FCC Part15B Class A, ICES-003, Class A

Safety

IEC 61508, EN 61508 SIL3, IEC 62061, EN 62061 SIL CL3, ISO/EN 13849-1:2015 Cat. 4, PL e

Dimensions

22.2×95×90 mm 0.87"×3.74"×3.54" (W×D×H)

Power supply

Power voltage

-

Power consumption

Max. 50 mA

Environmental resistance

Ambient temperature

−10 to +55 °C 14 to 131 °F (No freezing)

Storage temperature

-25 to +70 °C -13 to 158 °F (No freezing)

Relative humidity

5 to 85% (No condensation)

Operating altitude

Max. 2000 m 6561.7'

Overvoltage category

II

Pollution degree

2

Vibration resistance

Frequency: 5 to 9 Hz, Half amplitude: 3.5 mm 0.14"
Frequency: 9 to 150 Hz, Acceleration: 10 m/s2
10 times each in X, Y, Z directions

Shock resistance

Acceleration: 150 m/s2, Operating time: 11 ms, 3 times each in X, Y, Z directions

Material

Polycarbonate

Weight

Approx. 130 g

*1 Test outputs do not comply with paragraph 6.4 of IEC 61131-2.
*2 When the test output is branched and connected to multiple safety input devices, the total branched cable length must not exceed 400 m 1312.3'.

Other Models